Rockwell Automation Publication 193-UM015B-EN-P - June 2014 249
Metering and Diagnostics Chapter 7
Table 272 - Total Real Power (Parameter 67)
L1 Reactive Power
L1 Reactive Power (Parameter 68) reports the reactive power for line 1 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L1
Reactive Power is set to 0.
Table 273 - L1 Reactive Power (Parameter 68)
L2 Reactive Power
L2 Reactive Power (Parameter 69) reports the reactive power for line 2 in kVAR
or MVAR depending on the configuration value for Power Scale (Parameter
377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L2
Reactive Power is set to 0.
Table 274 - L2 Reactive Power (Parameter 69)
Default Value 0.000
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kW or MW
Default Value 0.000
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR or MVAR
Default Value 0.000
Minimum Value -2000000.000
Maximum Value 2000000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVAR or MVAR