Rockwell Automation Publication 193-UM015B-EN-P - November 2013 353
Parameter List Appendix B
Output Setup
Continued
312 OutPt01ComFltAct Output Pt01 action on comms
fault
BOOL 1 1 0= GoToCommFltValue
1= HoldLastState
0
313 OutPt01ComFltVal Output Pt01 value on comms
fault
BOOL 1 1 0=Open
1=Closed
0
314 OutPt01ComIdlAct Output Pt01 action on comms
idle
BOOL 1 1 0= GoToCommIdlValue
1= HoldLastState
0
315 OutPt01ComIdlVal Output Pt01 value on comms idle BOOL 1 1 0=Open
1=Closed
0
316 OutPt02PrFltAct Output Pt02 action on protection
fault
BOOL 1 1 0= GoToPrFltValue
1= IgnoreIfPossible
0
317 OutPt02PrFltVal Output Pt02 value on protection
fault
BOOL 1 1 0=Open
1=Closed
0
318 OutPt02ComFltAct Output Pt02 action on comms
fault
BOOL 1 1 0= GoToCommFltValue
1= HoldLastState
0
319 OutPt02ComFltVal Output Pt02 value on comms
fault
BOOL 1 1 0=Open
1=Closed
0
320 OutPt02ComIdlAct Output Pt02 action on comms
idle
BOOL 1 1 0= GoToCommIdlValue
1= HoldLastState
0
321 OutPt02ComIdlVal Output Pt02 value on comms idle BOOL 1 1 0=Open
1=Closed
0
322 OutDig1PrFltAct Digital Expansion Module 1
Outputs action on protection
fault
BOOL 1 1 0= GoToPrFltValue
1= Ignore
0
323 OutDig1PrFltVal Digital Expansion Module 1
Outputs value on protection fault
BOOL 1 1 0=Open
1=Closed
0
324 OutDig1ComFltAct Digital Expansion Module 1
Outputs action on comms fault
BOOL 1 1 0= GoToCommFltValue
1= HoldLastState
0
325 OutDig1ComFltVal Digital Expansion Module 1
Outputs value on comms fault
BOOL 1 1 0=Open
1=Closed
0
326 OutDig1ComIdlAct Digital Expansion Module 1
Outputs action on comms idle
BOOL 1 1 0= GoToCommIdlValue
1= HoldLastState
0
327 OutDig1ComIdlVal Digital Expansion Module 1
Outputs value on comms idle
BOOL 1 1 0=Open
1=Closed
0
328 OutDig2PrFltAct Digital Expansion Module 2
Outputs action on protection
fault
BOOL 1 1 0= GoToPrFltValue
1= Ignore
0
329 OutDig2PrFltVal Digital Expansion Module 2
Outputs value on protection fault
BOOL 1 1 0=Open
1=Closed
0
330 OutDig2ComFltAct Digital Expansion Module 2
Outputs action on comms fault
BOOL 1 1 0= GoToCommFltValue
1= HoldLastState
0
331 OutDig2ComFltVal Digital Expansion Module 2
Outputs value on comms fault
BOOL 1 1 0=Open
1=Closed
0
332 OutDig2ComIdlAct Digital Expansion Module 2
Outputs action on comms idle
BOOL 1 1 0= GoToCommIdlValue
1= HoldLastState
0
333 OutDig2ComIdlVal Digital Expansion Module 2
Outputs value on comms idle
BOOL 1 1 0=Open
1=Closed
0
334 OutDig3PrFltAct Digital Expansion Module 3
Outputs action on protection
fault
BOOL 1 1 0= GoToPrFltValue
1= Ignore
0
335 OutDig3PrFltVal Digital Expansion Module 3
Outputs value on protection fault
BOOL 1 1 0=Open
1=Closed
0
336 OutDig3ComFltAct Digital Expansion Module 3
Outputs action on comms fault
BOOL 1 1 0= GoToCommFltValue
1= HoldLastState
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units