Rockwell Automation Publication 193-UM015B-EN-P - November 2013 369
Parameter List Appendix B
Analog4 Setup
(continued)
547 InAMod4C1WarnLvl Level (in selected Units) where
Analog Input generates a
warning
UINT 2 1 0 65535 0
548 InAnMod4Ch02Type Assignment for Analog Module 4
Input Channel 02 function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
6= 100Pt385
7= 200Pt385
8= 500Pt385
9= 1000Pt385
10=100Pt3916
11= 200Pt3916
12= 500Pt3916
13= 1000Pt3916
14= 10Cu426
15= 120Ni618
16= 120Ni672
17= 604NiFe518
18= 150ohm
19= 1000ohm
20 = 3000ohm
21= 6000ohm
0
549 InAMod4Ch2Format Assignment for Analog Module 4
Input Channel 02 Data Format
USINT 1 1 0= EngUnits
1= EngUnitsTimes10
2= RawProportional
3= ScaledForPID
0
550 InAMod4C2TmpUnit Assignment for Analog Module 4
Input Channel 02 Temperature
Units
USINT 1 1 0=DegreesC
1=DegreesF
0
551 InAMod4C2FiltFrq Indicates Analog Module 4 Input
Channel 02 Filter Freq
USINT 1 1 0=17Hz
1=4Hz
2=62Hz
3=470Hz
0
552 InAMod4C2OpCktSt Indicates Analog Module 4 Input
Channel 02 Open Circuit State
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
553 InAnMod4Ch2RTDEn Enable Analog Module 4 Input
Channel 02 to function with RTD
BOOL 1 1 0=Disable
1=Enable
0
554 InAMod4C2TripDly Analog Module 4 Input Channel
02 Trip Delay
USINT 1 10 0 250 10 Sec
555 InAMod4C2TripLvl Level (in selected Units) where
Analog Input generates a trip
UINT 2 1 0 65535 0
556 InAMod4C2WarnLvl Level (in selected Units) where
Analog Input generates a
warning
UINT 2 1 0 65535 0
557 OutAnMod4Type Assignment for Analog Module 4
Output function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units