11-14
SP600 AC Drive User Manual
Enables/disables the compensation correction options.
Bit 0 - Reflect Wave
Enables/disables reflected wave correction software, which
reduces overvoltage transients from the drive to the motor. For
lead lengths beyond 300 feet, enable this feature.
Bit 1 - Enable Jerk
Enables/disables the jerk limit in the current limiter that helps to
eliminate overcurrent trips on fast accelerations. Disable this
feature if your application requires the actual acceleration of the
motor to be faster than .25 sec.
Bit 2 - Ixo AutoCalc
Calculates voltage drop due to leakage inductance (see
parameter 64).
56 Compensation
Range: See figure 11.5
Default: See figure 11.5
Access: 2 Path: Motor Control>Torq Attributes
See also:
Figure 11.5 – Compensation (56)
1
xxxxxxxxxxxxxx
10 01234567891112131415
1
=Enabled
0
=Disabled
x =Reserved
Bit #
Factory Default Bit Values
Reflect Wave
Enable Jerk
Ixo AutoCalc
Nibble 1Nibble 2Nibble 3Nibble 4
1