12-12
SP600 AC Drive User Manual
12.5.3 Fault Descriptions and Corrective Actions
Table 12.7 describes drive faults and corrective actions. It also
indicates if the fault is
Auto-resettable
Non-resettable
User-configurable
Table 12.7 – Fault Descriptions and Corrective Actions
Fault
No.
Type
Description Action
Analog In
Loss
29
An analog input is
configured to fault on
signal loss. A signal loss
has occurred.
Configure with Anlg In
1, 2 Loss (324, 327).
1. Check parameters.
2. Check for broken/loose
connections at inputs.
Anlg Cal
Chksum
108
The checksum read
from the analog
calibration data does
not match the
checksum calculated.
Replace drive.
Auto Rstrt
Tr ies
33
Drive unsuccessfully
attempted to reset a
fault and resume
running for the
programmed number of
Auto Rstrt Tries (174).
Enable/disable with
Fault Config 1 (238).
Correct the cause of the
fault and manually clear.
AutoTune
Aborted
80
The autotune procedure
was canceled by the
user.
Restart procedure.
DB
Resistance
69
Resistance of the
internal DB resistor is
out of range.
Replace resistor.