11-52
SP600 AC Drive User Manual
Enables/disables a feature to automatically load the present auto
frequency reference value into the OIM when Manual is selected.
Allows smooth speed transition from Auto to Manual mode. You can
adjust the manual speed setpoint from the OIM.
Enables/disables the feature that saves the present MOP (motor-
operated potentiometer) frequency reference at power down or at
stop.
Sets the rate of change of the MOP reference in response to a MOP
inputs.
193 Man Ref Preload
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>OIM Ref Config
See also: 320 - 327, 361 - 366
194 Save MOP Ref
Range: See figure 11.15
Default: At Pwrdown
Access: 2 Path: Utility>MOP Config
See also:
Figure 11.15 – Save MOP Ref (194)
0
xxxxxxxxxxxxxx
10 01234567891112131415
1
=Save
0
=Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
At Stop
Nibble 1Nibble 2Nibble 3Nibble 4
0
195 MOP Rate
Range: 0.2 to Maximum Freq [0.1 Hz/sec]
Default: 1.0 Hz/sec
Access: 2 Path: Utility>MOP Config
See also: