SP600 AC Drive User Manual
Indicates Type 1 alarm conditions that currently exist in the drive.
Note that for alarm conditions not configured in Alarm Config 1
(259), the status indicated will be a zero.
Refer to chapter 12, Troubleshooting the Drive, for more information
about alarms.
Indicates Type 2 alarm conditions that currently exist in the drive.
Refer to chapter 12, Troubleshooting the Drive, for more information
about alarms.
211 Drive Alarm 1
Range: See figure11.20
Default: Read Only
Access: 1 Path: Utility>Diagnostics
Utility>Alarms
See also: 212, 259
Figure 11.20 – Drive Alarm 1 (211)
000000
x
000
xxxxxx
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Reserved
Drv OL Lvl 1
Drv OL LVl 2
Decel Inhibit
Waking
Nibble 1Nibble 2Nibble 3Nibble 4
212 Drive Alarm 2
Range: See figure 11.21
Default: Read Only
Access: 1 Path: Utility>Diagnostics
Utility>Alarms
See also: 211
Figure 11.21 – Drive Alarm 2 (212)
00000000000
xx0x
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
DigIn CflctA
DigIn CflctB
DigIn CflctC
Bipolr Cflct
MtrTyp Cflct
NP Hz Cflct
MaxFrq Cflct
VHz NegSlope
IR Vlts Rang
FlxAmps Rang
SpdRef Cflct
Ixo Volt Rang
Sleep Config
Dig In Value
Nibble 1Nibble 2Nibble 3Nibble 4
UserSetCflct
0