Troubleshooting the Drive
12-19
12.6 Common Symptoms and Corrective Actions
Table 12.9 – Drive Does Not Start From Terminal Block Logic
Indication(s) Cause(s) Corrective Action
Flashing red
Ready LED.
Drive is faulted. Clear fault:
Press OIM stop key if
that OIM is control
source.
•Cycle power.
Set Fault Clear (240) to
1.
Toggle terminal block
stop or terminal block
reset digital input if
terminal block is the
control source.
Incorrect operation
from the terminal
block.
Incorrect input wiring.
2-wire control requires
Run, Run Forward, or
Run Reverse input(s).
3-wire control requires
Start and Stop inputs
Jumper from terminal 7
to 8 is required.
Wire inputs correctly
and/or install jumper.
Incorrect digital input
programming.
Mutually exclusive
choices have been
made.
2-wire and 3-wire
programming may be
conflicting.
Exclusive functions (i.e,
direction control) may
have multiple inputs
configured.
Stop if factory default and
is not wired or is open.
Start or Run
programming may be
missing.
Program Digital In”x” Sel
(361-366) for correct
inputs.
Logic Source Sel is not set
to Terminal Blk.
Set Logic Source Sel to
Terminal Blk.