12-4
SP600 AC Drive User Manual
12.3 Determining Drive Status Using the Ready LED
Figure 12.3 – Location of the Ready LED
Network
Status
LEDs
(Refer to
network
manuals.)
Ready LED
See table 12.2
Table 12.2 – Ready LED Status Definitions
Color State Description
Green Flashing Drive ready, but not running and no faults
are present.
Steady Drive running, no faults are present.
Ye l lo w
See section
12.4.
Flashing The drive is not ready. Check parameter
214 (Start Inhibits).
Steady An alarm condition exists.
Check parameters 211 (Drive Alarm 1)
and 212 (Drive Alarm 2).
Red
See section
12.5.
Flashing A fault has occurred.
Steady A non-resettable fault has occurred.