
Parameter Descriptions
11-94
Selects the drive status that will energize an output relay.
Sets the relay activation level for options 10-15 in Digital Out2 Sel
(384). Units are assumed to match the above selection
(i.e., At Freq = Hz, At Torque = Amps).
Sets the on delay time for the digital outputs. This is the time
between the occurrence of a condition and activation of the relay.
Sets the off delay time for the digital outputs. This is the time
between the disappearance of a condition and de-activation of the
relay.
See also:
1-4, 12, 48, 53, 137, 147, 157, 184, 218, 381-383, 385,
386
1
Any relay programmed as fault or alarm will energize (pick up) when power
is applied to the drive and de-energize (drop out) when a fault or alarm
exists. Relays selected for other functions will energize only when that
condition exists and will de-energize when the condition is removed.
2
Activation level is defined in Dig Out “x” level (381, 385).
384 Digital Out1 Sel
385 Dig Out2 Level
Range: 0.0 to 819.2 [0.1]
Default: 0.0
Access: 1 Path: Inputs & Output>Digital Outputs
See also: 380
386 Dig Out2 OnTime
Range: 0.00 to 600.00 Sec [0.01 Sec]
Default: 0.00 Sec
Access: 2 Path: Inputs & Output>Digital Outputs
See also: 380
387 Dig Out2 OffTime
Range: 0.00 to 600.00 Sec [0.01 Sec]
Default: 0.00 Sec
Access: 2 Path: Inputs & Output>Digital Outputs
See also: 380
Comentarios a estos manuales