Parameter Descriptions
11-71
Present frequency reference scaled as a DPI reference for peer-to-
peer communications. The value shown is the value after the accel/
decel ramp but prior to any corrections supplied by slip comp, PI,
etc.
Disables manual mode activation from the port corresponding to bit
number.
Example:
Bit 0 = 0 Terminal block disabled
Bit 1 = 1 Local OIM enabled
In this example, manual mode can be selected by the OIM but not
by terminal block inputs.
273 Drive Ramp Rslt
Range: 0 to 32767 [1]
Default: Read Only
Access: 2 Path: Communication>Comm Control
See also:
286 Manual Mask
Range: See figure 11.32
Default: 0x2F
Access: 2 Path: Communication>Masks & Owners
See also:
Figure 11.32 – Manual Mask (286)
1111
x
1
xxxxxxxxxx
10 01234567891112131415
1
= Control is Enabled
0
= Control is Disabled
x =Reserved
Bit #
Factory Default Bit Values
Terminal Blk
Local OIM
DPI Port 2
DPI Port 3
Reserved
Network
Reserved
Nibble 1Nibble 2Nibble 3Nibble 4