11-26
SP600 AC Drive User Manual
Specifies which signal source is being used as a trim input. The trim
is an input signal which is added to the reference A signal. If an
analog input is used as the trim signal, two scaling parameters are
provided.
117 Trim In Select
Range: 1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = Reserved
22 = Network
23 = Reserved
Default: 2 = Analog In 2
Access: 2 Path: Speed Command>Speed Trim
See also: 90, 93
Figure 11.8 – Trim Input Select
(117)
(118)
Select
Reference A
+
+
Tr i mm e d
Reference A