Finding Wire-Routing Locations and Grounding
5-3
Figure 5.2 – Wire Routing and Terminal Block Locations (Frame 5 Shown)
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75° C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT ACOUTPUT
Optional
Communications
Module
9
60 to 75 HP 100 HP
Input Power Wiring
Motor Wiring
I/O and Signal
Wiring
I/O and Signal
Wiring
Te r min al
Shield
Power Terminal
Block
Signal and Control
Terminal Block