11-56
SP600 AC Drive User Manual
1 = DynUsrSetSel: DynUsrSetSel (205) determines the active User
Set.
Controls which User Set is in memory when Ctrl Source (bit 1) of
DynUsrSetCnfg (204) is set to DynUsrSetSel.
Bit 0 - UserSetBit0
0 = Disabled
1 = Enabled
Bit 1 -UserSetBit1
0 = Disabled
1 =Enabled
Figure 11.16 – Dyn UserSet Cnfg
205 DynUsrSetSel
Range: See figure 11.17.
Default: See figure 11.17.
Access: 2 Path: Utility>Drive Memory
See also: 204, 206
0
xx
0
xxxxxxxxxxxx
10 01234567891112131415
Bit 0:
1
=Enabled
0
=Disabled
Bit 1:
1 = DynUsrSetSel
0 = Digital Inputs
x = Reserved
Bit #
Factory Default Bit Values
Dynamic Mode
Ctrl Source
Nibble 1Nibble 2Nibble 3Nibble 4
Table 11.4 – Dynamic User Set Mode
UserSetBit1 UserSetBit0 UserSet Loaded in Memory
0 0 User Set 1
0 1 User Set 2
1 0 User Set 3
1 1 User Set 3