Parameter Descriptions
11-25
.
Scales the lower value of the TB Man Ref Sel selection when the
source is an analog input. This parameter should be set in
conjunction with parameter 323 or 326, depending on the analog
input being used.
Sets the output frequency when a jog command is issued. The jog
function can be activated using the OIM or terminal block
assignments.
Provides an internal fixed speed command value when
Speed Ref A = Preset Spd 1-7. The preset speed is selected by the
configuration of the Dig In # speed select functions.
98 TB Man Ref Lo
Range: -/+Maximum Speed [0.1 Hz]
Default: 0.0 Hz
Access: 1 Path: Speed Command>Speed References
See also: 96, 323, 325
100 Jog Speed
Range: 0 to Maximum Speed [0.1 Hz]
Default: 10.0 Hz
Access: 0 Path: Speed Command>Discrete Speeds
See also:
101
102
103
104
105
106
107
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
Range: -/+ Maximum Speed [0.1 Hz]
Default: See table 11.2
Access: 2 Path: Speed Command>Discrete Speeds
See also: 90, 93
Table 11.2 – Default Values for Preset Speeds 1-7
Parameter No. Parameter Name Default
101 Preset Speed 1 5.0 Hz
102 Preset Speed 2 10.0 Hz
103 Preset Speed 3 20.0 Hz
104 Preset Speed 4 30.0 Hz
105 Preset Speed 5 40.0 Hz
106 Preset Speed 6 50.0 Hz
107 Preset Speed 7 60.0 Hz