11-68
SP600 AC Drive User Manual
Enables/disables annunciation of the faults shown in figure 11.29.
Resets a fault and clears the fault queue.
Enables/disables a fault reset (clear faults) attempt from any source.
This does not apply to fault codes stored in the fault queue, which
are cleared indirectly via other actions.
238 Fault Config 1
Range: See figure 11.29
Default: See figure 11.29
Access: 2 Path: Utility>Faults
See also:
Figure 11.29 – Fault Config 1 (238)
1x100
0xxxxxxxxx
10 01234567891112131415
1
=Enabled
0
=Disabled
x =Reserved
Bit #
Factory Default Bit Values
Power Loss
UnderVoltage
Motor OverLd
Shear Pin
AutRst Tries
Decel Inhibit
Nibble 1Nibble 2Nibble 3Nibble 4
1
240 Fault Clear
Range: 0 = Ready
1 = Clear Faults
2 = Clr Flt Que
Default: 0 = Ready
Access: 2 Path: Utility>Faults
See also: 241
241 Fault Clear Mode
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>Faults
See also: 240