About the Drive
2-18
2.4.1 Essential Requirements for CE Compliance
All conditions listed below must be satisfied for SP600 drives to
meet the requirements of EN61800-3 for the Second Environment
(Industrial).
• Standard SP600 CE-compatible drive.
• Grounding as described in section 5.3 if this manual.
• Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
• Cable length restrictions, common mode cores and filters per
table 2.2.
Table 2.3 – SP600 AC Drive EN1800-3 EMC Compatibility
Frame
Drive Description Second Environment
First Environment
Restricted
Distribution
2 Drive with any options
Restrict Motor Cable
to 30 m (98 ft)
- Restrict Motor Cable
to 150 m (492 ft)
- Install external filter
1
1
Select the Deltron Emcom (http://www.deltron--emcom.com) filter (or equivalent)
that meets your specifications from the list below.
Filter Part No.
Current Filter Part No. Current
MIF306 6 A MIF350 50 A
MIF310 10 A MIF375 75 A
MIF316 16 A MIF3100 100 A
MIF323 23 A MIF3150 150 A
MIF330 30 A
3 Drive with any options
4
5
6
Drive with any options (Not Available)