Selects whether the internal or an external DB resistor option will be
used. An internal DB resistor is one that can be mounted inside the
footprint of the drive. External DB resistors are panel mounted
separately.
Proportional gain for the bus regulator. Used to adjust regulator
response.
163 DB Resistor Type
Range: 0 = Internal Res
1 = External Res
2 = None
Default: 0 = Internal Res
Access: 1 Path: Dynamic Control>Stop/Brake Modes
See also: 161, 162
!
ATTENTION: AC drives do not offer protection for
externally mounted brake resistors. A risk of fire
exists if external braking resistors are not protected.
External resistor packages must be self-protected
from overtemperature or the protective circuit shown
below, or equivalent, must be supplied.
Power On
R (L1)
S (L2)
T (L3)
Power Source DB Resistor Thermostat
Power Off
M
M
(Input Contactor) M
Three-Phase
AC Input
AC Drive
164 Bus Reg Kp
Range: 0 to 10000
Default: 1200
Access: 2 Path: Dynamic Control>Stop/Brake Modes
See also: