Parameter Descriptions
11-59
Present operating condition of the drive.
Figure 11.19 – Drive Status 2 (210)
0000000
x
000000
xx
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
Nibble 1Nibble 2Nibble 3Nibble 4
Bit Name Description
0 Ready No start inhibits are active.
1 Active Drive is generating output voltage to the motor.
2 Running Drive is generating output voltage to the motor,
run has been selected.
3 Jogging Drive is in jog mode.
4 Stopping Drive is stopping.
5 DC Braking DC braking is active.
6 Auto Tuning Tuning function is active.
8 AutoRst Ctdn: Auto Restart Countdown. Refer to parameter 174.
9 AutoRst Ac: Auto Restart Active. Refer to parameter 174.
10 Curr Limit: Drive is in current limit.
11 Bus Freq Reg: Drive is regulating bus frequency.
12 Motor Overld: Motor overload is active.
13 DPI @ 500 K DPI communications is operating at 500 kbaud
(1), 125 kbaud (0)