9-6
SP600 AC Drive User Manual
9.4 Speed Reference
The default configuration is for keypad reference source. If you want
to use an analog reference input for control, you must configure the
analog reference inputs. The example below shows speed
reference from an analog voltage input. Analog inputs can also be
configured for 4 to 20 mA.
9.5 Changing the Speed of the Drive (Setpoint
Control)
OIM arrows only work to set speed changes when the LCD display
is in the monitor mode.
If you select manual mode from the keypad (OIM) then the manual
speed setpoint is set by the arrow keys.
Figure 9.5 – Analog Speed Reference
2225
Analo
g
In 1 (
-
)
C
om
m
on
+10 VD
C
An
al
og
In 1
(+
)
1
Analog Reference Wiring (Voltage)
(90) Speed Ref A Sel = Analog In1
(91) Speed Ref Hi = 60 Hz
(92) Speed Ref Lo = 0 Hz
(P320) Analog In Config = .xx00
(P322) Analog In Hi = 10.0 V
(P323) Analog In Lo = 0.0 V