Selects the type of input signal being used for analog input 1 and 2.
These inputs can be configured as 0 to 10 VDC or 4 to 20 mA
inputs.
Enables/disables the square root function for each analog input.
This function should be enabled if the input signal being monitored
varies with the square of the quantity. The square root function is
scaled such that the input range is the same as the output range.
For example, if the input is set up as a unipolar voltage input, then
the input and output ranges of the square root function will be 0 to
10 volts.
320 Anlg In Config
Range: See figure 11.35
Default: See figure 11.35
Access: 0 Path: Inputs & Outputs>Analog Inputs
See also: 322, 323, 325, 326
Figure 11.35 – Anlg In Config (320)
0
xx
1
xxxxxxxxxxxx
10 01234567891112131415
1
=Current
0
=Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1Nibble 2Nibble 3Nibble 4
321 Anlg In Sqr Root
Range: See figure 11.36
Default: See figure 11.36
Access: 2 Path: Inputs & Outputs>Analog Inputs
See also:
Figure 11.36 – Anlg In Sqr Root (321)
0
xx
0
xxxxxxxxxxxx
10 01234567891112131415
1
=Enable
0
=Disable
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1Nibble 2Nibble 3Nibble 4