Rockwell-automation SP600 User Manual Version 3.0 Manual de usuario Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 274
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
Mounting the Drive
3-5
3.1.2 Making Sure Environmental Conditions are Met
Before deciding on an installation site, consider the following
guidelines:
Verify that NEMA 1 drives can be kept clean, cool, and dry.
The area chosen should allow the space required for proper air
flow as defined in section 3.1.3.
Be sure that NEMA 1 drives are away from oil, coolants, or other
airborne contaminants.
Do not install the drive more than 3300 feet above sea level
without derating output power. For every 300 feet above 3300
feet, derate the output current 1%.
Verify that the drive location will meet the environmental
conditions in Appendix A.
Figure 3.2 – Selecting Input Phase and Fan Voltage (60HP and Larger)
480 Volt Tap
600 Volt Tap
690 Volt Tap
400 Volt Tap
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75° C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT ACOUTPUT
Optional
Communications
Module
9
Line Type
Three-Phase
(default)
Single-Phase
Spare
Spare
x 4
Vista de pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 273 274

Comentarios a estos manuales

Sin comentarios