Parameter Descriptions
11-55
Resets selected parameters that change the drive voltage rating,
current rating, scaling, and motor data. Maximum Frequency (55)
will be affected by changing this parameter.
Important: On frame 5 and 6 drives, the internal fan voltage may
have to be changed when using options 2 or 3. See
section 3.1.1.4.
Provides a checksum value that indicates whether or not a change
in drive programming has occurred (data values only).
Configures behavior of User Sets. Dynamic switching between sets
is permitted from either digital input states of parameter value.
Bit 0 - Dynamic Mode - Specifies User Sets operating mode.
0 = Disabled: Disabled causes normal operation.
1 = Enabled: Enabled selects Dynamic Mode. While enabled,
parameters changes are not saved in active non-volatile storage.
Bit 1 - Ctrl Source - Defines which source controls the selection of
user sets, while Dynamic Mode is enabled.
0 = Dig. Inputs: Dig. Inputs refers to UserSetBitn defined by
Terminal Block Input(s) from Digital ln 1-6 Sel (361-366).
202 Voltage Class
Range: 2 = Low Voltage
3 = High Voltage
Default: Based on Drive Type
Access: 2 Path: Utility>Drive Memory
See also: 55
203 Drive Checksum
Range: 0 to 65535 [1]
Default: Read Only
Access: 2 Path: Utility>Drive Memory
See also:
204 Dyn UserSet Cnfg
Range: See figure 11.16.
Default: See figure 11.16.
Access: 2 Path: Utility>Drive Memory
See also: 205, 206, 361-366