7-4
SP600 AC Drive User Manual
11 Digital Out 1 – N.C. Fault Resistive Load
Rating: 2 A at 250 V AC/30 V DC
Min. Load: 10 mA
Inductive Load
Rating: 2 A at 250 V AC/30 V DC
Min. Load: 10 mA
380 -
387
12 Digital Out 1
Common
13 Digital Out 1 – N.O.
14 Digital Out 2 – N.C. Running
15 Digital Out 2
Common
16 Digital Out 2 – N.O.
Analog Inputs
17 Anlg Current In 1 (–)
1
Isolated
2
,
4-20 mA
, 11 bit & sign,
124 ohm input
impedance.
320 -
329
18 Anlg Current In 1 (+)
19 Anlg Current In 2 (–)
1
Isolated
2
, 4-20 mA, 11 bit & sign,
124 ohm input impedance.
20 Anlg Current In 2 (+)
Voltage Reference Supplies
21 –10V Pot Reference n/a 2k ohm minimum, 15 mA
maximum load.
22 +10V Pot Reference n/a
23 Reserved
24 +24VDC n/a Drive supplied power for logic
inputs. 150 mA maximum Load.
Voltage Reference Supplies (cont.)
25 Digital In Common n/a
Table 7.1 – Wiring Signal and Control I/O to the Terminal Block
No. Signal
Factory
Default Description
Related
Param.
1
16
32
Comentarios a estos manuales