Rockwell-automation SP600 User Manual Version 3.0 Manual de usuario Pagina 174

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 274
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 173
11-72
SP600 AC Drive User Manual
Inputs that are presently issuing a valid stop command.
Indicates the source providing manual control and reference.
288 Stop Owner
Range: See figure 11.33
Default: Read Only
Access: 2 Path: Communication>Masks & Owners
See also: 276 - 285
Figure 11.33 – Stop Owner
0000
x
0
xxxxxxxxxx
10 01234567891112131415
1
=Issuing Command
0
=No Command
x =Reserved
Bit #
Terminal Blk
DPI Port 1
DPI Port 2
DPI Port 3
Reserved
DPI Port 5
Reserved
Nibble 1Nibble 2Nibble 3Nibble 4
Source Location
Terminal Block Logic I/O
DPI Port 1 Local OIM
DPI Port 2 DIN port at base of drive
DPI Port 3 Split DIN port
DPI Port 5 (Network) Network option
298 Manual Owner
Range: See figure 11.34
Default: Read Only
Access: 2 Path: Communication>Masks & Owners
See also:
Figure 11.34 – Manual Owner
0000
x
0
xxxxxxxxxx
10 01234567891112131415
1
= Control is Enabled
0
= Control is Disabled
x =Reserved
Bit #
Factory Default Bit Values
Terminal Blk
Local OIM
DPI Port 2
DPI Port 3
Reserved
Network
Reserved
Nibble 1Nibble 2Nibble 3Nibble 4
Vista de pagina 173
1 2 ... 169 170 171 172 173 174 175 176 177 178 179 ... 273 274

Comentarios a estos manuales

Sin comentarios