Rockwell-automation SP600 User Manual Version 3.0 Manual de usuario Pagina 230

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 274
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 229
A-6
SP600 AC Drive User Manual
Selectable Motor Control Sensorless Vector with full tuning. Standard
V/Hz with full custom capability.
Stop Modes Multiple programmable stop modes including
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S-curve.
Accel/Decel Two independently programmable accel and
decel times. Each time may be programmed
from 0 - 3600 seconds in 0.1 second
increments.
Table A.5 – Control Specifications
Table A.6 – Analog Interface Specifications
Analog Input 1,
Differential Voltage Input
Signal level
Differential Input resistance
Isolation
Resolution
Input processing period
-10V to +10V
100kΩ
160V
11 bits plus sign
5ms
Analog Input 1,
Differential Current Input
Signal level
Differential Input resistance
Resolution
Input processing period
0(4) to 20mA
124Ω
11 bits plus sign
5ms
Analog Input 2,
Differential Voltage Input
Signal level
Differential Input resistance
Initial accuracy (@25°C)
Resolution
Input processing period
-10V to +10V
100kΩ
160V
11 bits plus sign
5ms
Analog Input 2,
Differential Current Input
Signal level
Differential Input resistance
Resolution
Input processing period
0(4) to 20mA
124Ω
11 bits plus sign
5ms