Rockwell-automation 2071-Axx Kinetix 3 Component Servo Drive Serial Ho Manual de usuario Pagina 90

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 146
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 89
90 Rockwell Automation Publication 2071-RM001B-EN-P - April 2013
Appendix A Standard Drive Parameters
Group 4 - Torque Controls
[Pr - 4.00] Current Scale
Ultraware Name Current Scale
Internal Value
(1)
(1) Internal Value used for Modbus reading/writing functions
Display Value
Range 0…1000 0…100.0
Default 333 33.3
Units 0.1% of rated continuous current/V % of rated continuous current/V
When Enabled Servo-Off -> Setting
Applicable Operating Mode Analog Current command, Dual current Command
Modbus Address 400
[Pr - 4.01] Positive Internal Current Limit
Ultraware Name Current Limits: Positive Internal
Range 0…500
Default 300
Units % of motor rated continuous current
When Enabled Immediately
Applicable Operating Mode All
Modbus Address 401
[Pr - 4.02] Negative Internal Current Limit
Ultraware Name Current Limits: Negative Internal
Range 0…500
Default 300
Units % of motor rated continuous current
When Enabled Immediately
Applicable Operating Mode All
Modbus Address 402
[Pr - 4.03] Positive External Current Limit
Ultraware Name Current Limits: Positive External
Range 0…500
Default 100
Units % of motor rated continuous current
When Enabled Immediately
Applicable Operating Mode All
Modbus Address 403
Vista de pagina 89
1 2 ... 85 86 87 88 89 90 91 92 93 94 95 ... 145 146

Comentarios a estos manuales

Sin comentarios